HAZOP - Ammonia Refrigeration Plant - Rhetorical Questions

 

Hi everyone, I would like to share some notes and questions I made during a HAZOP (Hazard Operability) safety study of an Ammonia Refrigeration Plant Room.

Ammonia is used to chill water in a heat exchanger system. The system consist of compressors, chillers, heat exchangers, liquid receiver vessels, gas detection, etc. 

Like my other posts, questions here can be asked for any generic process plants.

Please comment, like and subscribe.

Photograph 1: Generic refrigeration pipework

1.      Is there mandatory gas monitor (RPE) requirements for personnel entering the plant room?

(1)   Is there signage requiring gas monitors present?

(2)   Is it included in contractor rules / induction?

(3)   Can a radio system be used to inform a person the actual ammonia concentration prior to entering in the room?

(4)   Are isolation valves readily visible, operatable and indicated on a P&IDs, and on display on the wall of the room?

 

2.      Inadequate isolation procedures - Is there double isolation on maintenance lines handling ammonia?

(1)   Can you consider relying on double isolation of charging of ammonia

(2)   This should stop the plant but does not remove the ammonia system – e.g. compressors, evaporators and condensers

(3)   Or is complete removal of ammonia needed? e.g. from liquid receivers and/or spray chillers

 

3.      Can a leak in ammonia cause lighting to be switched off by alarm activation at high level?

(1)   Can you consider temporary solution of leaving access door open when someone is in ammonia room?

(2)   Is there painted hand rail/floor as guide to emergency exit?

 

4.      Is there any fire extinguishers in ammonia plant room? - This should be removed as temptation to tackle fire may expose an operator to toxic ammonia releases

 

5.      Can you have extract fans running permanently at low speeds – so they are ready to start when required? E.g. activation from a gas detector, etc.

 

Photograph 2: Extraction fan in ammonia plant room

Chiller & evaporator system:

6.      Is there any consequence for ammonia leaking into water tubes of a chiller system?

(1)   Alkaline water in chilling process…

(2)   Mixing usually creates a vacuum – Is chiller vessel rated for full vacuum?

(3)   Sampling taken by lab technician and potential exposure?

 

7.      Is failure of electrical trace heating an issue?

(1)   Lack of heating oil and oil cools, thus ammonia is not evaporated efficiently

(2)   Could you install stick-on digital temperature indicators? to put on to the vessel

(3)   Include checking as part of daily walk through by operator

 

8.      Are heat exchangers subject to the statutory inspection under the Pressure System Safety Regulations (PSSR)? If so then undertake inspection and implement the findings

Photograph 3: Generic compressors for ammonia circulation

Compressor

9.      For the compressor outlet valve, can you cap the valve stem, as a safeguard? Therefore only tools would be required to close valve – thus prevent inadvertent closing of the valve.

 

10.   Does a failure in oil heater element, due to high temperature trip - have a ‘fail off’ or ‘fail on’ mode? Could the oil heater stay on, in a failure mode (high temperature)?

 

11.   Can the lube oil separator fail on start-up – leading to low temperature? Is there automated shut off system and manual daily oil level checks undertaken for this?



Pressure relief

12.   Can you add a manifold (multiple) of the pressure relief valve lines? Should there be separate lines to atmosphere? (for multiple PSVs)?

 

13.   Can you install a sight glass after a pressure relief valve – if it is blocked or fails to open?